sks
RSSPosts: 91
DEVICE FOR LEAD TENSIONING AND LOAD LIFTING
This device is used for overhead power lines tensioning and load lifting. One end of the device is attached to a pole, facade or similar fixed object. Moving handle activates the gear wheel which starts moving the chain. Assembling and usage are quick and easy. Maximum tension force is 0.75 and 1.5t. Standard length of the chain is 2 meters. At customers demand, we can deliver a longer chain.
- Code number: 6600206……for 0.75 t.
- Code number: 6601826……for 1.5 t.
ALUMINUM INSULATED JOINTS “FALIS”
Used for jointing of Aluminum and copper conductor cables, when connecting residential units and public buildings to distibutive power line.
Code number | Designation mm²/mm² | d1 mm | d2 mm | d3 mm | L mm | Package pcs | Weight g/100 pcs |
3501006 | FALIS 10/6 | 16 | 4.5 | 3.5 | 73 | 75 | 2.45 |
3501010 | FALIS 10/10 | 16 | 4.5 | 4.5 | 73 | 75 | 2.20 |
3501604 | FALIS 16/4 | 16 | 5.5 | 2.8 | 73 | 75 | 2.88 |
3501606 | FALIS 16/6 | 16 | 5.5 | 3.5 | 73 | 75 | 2.77 |
3501610 | FALIS 16/10 | 16 | 5.5 | 4.5 | 73 | 75 | 2.66 |
3501616 | FALIS 16/16 | 16 | 5.5 | 5.5 | 73 | 75 | 2.57 |
3502516 | FALIS 25/16 | 16 | 6.5 | 5.5 | 73 | 75 | 2.10 |
INSULATED WATERPROOF JOINTING SLEEVES – FID
These sleeves are used for connection of insulated Aluminum and copper conductors which are used for residential and commercial building connections to distribution network, as well as for jointing of conductors for distributive ABC cables voltage up to 1kV. FID sleeves with the cross sections up to 25mm2 are mainly used for jointing of house connections. FID-F sleeves with cross sections up to 35, 50 and 70mm2 are used for connecting distributive ABC phase conductors. FID-N sleeves with 70mm2 cross sections are used for connecting the supporting conductor of distributive ABC. All these sleeves are supplied with special insulation.
Hexagonal crimping is carried out directly through the insulation, which has excellent mechanical and electrical characteristics. The standard FEMAN tools with special die are used for crimping operation. Following the instruction on sleeve insulation, remove the terminal insulation to the required length. After that, conductors are pulled into sleeve through rubber seal thus preventing humidity penetration and appearance of electrolytic corrosion.
On insulation points and sequence are indicated where crimping should be made. For FID sleeves, depending on the thickness of the insert, two or three crimping operations are performed from the center towards left and right .FID-N sleeve for zero (supporting) conductor is somewhat longer considering that the joint is under mechanical loading, so therefore, up to six left and right crimping operations need to be done.
Code number | Designation mm²/mm² | d1 mm | d2 mm | d3 mm | L mm | Crimping die | Package pcs | Weight g/100 pcs |
3401006 | MJPB 10/6 | 18,5 | 4,5 | 3,5 | 70,5 | E 140 | 100 | 2,67 |
3401010 | MJPB 10/10 | 18,5 | 4,5 | 4,5 | 70,5 | E 140 | 100 | 2,56 |
3401604 | MJPB 16/4 | 18,5 | 5,5 | 2,8 | 70,5 | E 140 | 100 | 2,10 |
3401606 | MJPB 16/6 | 18,5 | 5,5 | 3,4 | 70,5 | E 140 | 100 | 1,94 |
3401610 | MJPB 16/10 | 18,5 | 5,5 | 4,3 | 70,5 | E 140 | 100 | 2,57 |
3401616 | MJPB 16/16 | 18,5 | 5,5 | 5,5 | 70,5 | E 140 | 100 | 2,52 |
3402510 | MJPB 25/10 | 18,5 | 6,5 | 5,5 | 70,5 | E 140 | 100 | 2,35 |
3402516 | MJPB 25/16 | 18,5 | 6,5 | 5,5 | 70,5 | E 140 | 100 | 2,28 |
3402525 | MJPB 25/25 | 18,5 | 6,5 | 6,5 | 70,5 | E 140 | 100 | 2,22 |
3403516 | MJPB 35/16 | 18,5 | 8 | 5,5 | 70,5 | E 140 | 100 | 2,35 |
3403525 | MJPB 35/25 | 18,5 | 8 | 6,5 | 70,5 | E 140 | 100 | 2,20 |
3403535 | MJPB 35/35 | 18,5 | 8 | 8 | 70,5 | E 140 | 100 | 2,09 |
3405025 | MJPT 50/25 | 23,5 | 9,3 | 6,5 | 103 | E 173 | 50 | 2,95 |
3405050 | MJPT 50/50 | 23,5 | 9,3 | 9,3 | 103 | E 173 | 50 | 3,09 |
3407016 | MJPT 70/16 | 23,5 | 11,2 | 5,5 | 103 | E 173 | 50 | 6,75 |
3407050 | MJPT 70/50 | 23,5 | 11,2 | 9,3 | 103 | E 173 | 50 | 6,50 |
3407070 | MJPT 70/70 | 23,5 | 11,2 | 11,2 | 103 | E 173 | 50 | 5,40 |
3409595 | MJPT 95/95 | 23,5 | 12,2 | 12,2 | 103 | E 173 | 50 | 5,04 |
3415454 | MJPT-N 50/50 | 23,5 | 9,3 | 9,3 | 170 | E 173 | 50 | 10,40 |
3417154 | MJPT-N 71/54 | 23,5 | 11,2 | 9,3 | 170 | E 173 | 50 | 9,70 |
3417171 | MJPT-N 71/71 | 23,5 | 11,2 | 11,2 | 170 | E 173 | 50 | 9,43 |
3419595 | MJPT-N 95/95 | 23,5 | 12,2 | 12,2 | 170 | E 173 | 50 | 9,10 |
AUTOMATIC GRIPPER FOR Al-Fe ROPE 8-24 mm
Used for tensioning of Al-Fe ropes with diameters from 8-24 mm. Made of steel alloy, while the contact pads are of aluminum alloy. If it is used for steel ropes and cables tensioning (please indicate when ordering) the pads are made of carbon steel. Maximum tension force is 2000 kg
- Length: 270 mm
- Weight: 3.5 kg
- Code number: 1884120
AUTOMATIC GRIPPER 6-14
Designed for pulling and tensioning of Aluminum and Aluminum-steel conductors with outer diameters between 6 and 14 mm. Its construction by lever system grips the conductor and while pulling automatically increases tension force of the grip to the conductor, providing quick and tight connection, for pulling and tensioning. Maximum tension force is 400 kg. This automatic gripper has built-in U-joint which enables quick and easy connection with the pulling device. This gripper is made of special Aluminum allow.
- Length: 308 mm
- Weight 1.5 kg
- Code number: 1884614
AUTOMATIC TIE-GUN FLY-600 L
Used for tightening cable splices of up to 13 mm width when wrapping and fixing cable bunches. This tie-gun has a tension regulator which enables cutting off access length on splices after regulated force of tension is applied.
SELF ADHESIVE PVC WARNING SIGN
This signs are made from Self extinguish plastic material, resistant to all wether conditions. These signs convey messages or warnings. Sheets are easy to bent, and easily adjusted to every form. We also manufacture custom signs (Please mark the text you wish to have on the sign when ordering).
- Dimensions: 320×150 mm
- Code: 4703200
SILICONE COMPOSITE SUPPORT INSULATING CHAINS
Silicone composite support insulators are used for MV uninsulated overhead lines from 10 to 35 kV. Made in accordance with IEC 6109-1992-03 standard. They are usually produced for mechanical loading force of 4000 daN. They are very light compared to ceramic and glass insulator sets providing quick and easy assembling. Corrosion protection is performed by Zn plating, but at the customer’s request we do hot-dip galvanization.
Code number | Type | Voltage kV | Rated voltage kV | Breaking force daN |
4890511 | Ste-Single chain support | 10 | 90 | 4000 |
4890521 | Ste-Single chain support | 20 | 130 | 4000 |
4890531 | Ste-Single chain support | 35 | 145 | 4000 |
4890512 | Ste-Double chain support | 10 | 90 | 4000 |
4890522 | Ste-Double chain support | 20 | 130 | 4000 |
4890532 | Ste-Double chain support | 35 | 145 | 4000 |
SILICON COMPOSITE TENSION INSULATOR CHAINS
Tension silicon composite insulators are used for tension and support hanging for non-insulated overhead lines from 10 to 35kV. They are made in accordance with IEC 6109 – 1992 -03 standard and usually produced for mechanical loading force of 4000 daN. They are very light compared to ceramic and glass insulator sets providing quick and easy assembling. Corrosion protection is usually performed by cold galvanization, but at the customer’s request we do hot-dip galvanization.
Code number | Type | Voltage kV | Rated voltage kV | Breaking force daN |
4890311 | Set – single with wedge shape | 10 | 90 | 4000 |
4890321 | Set – single with wedge shape | 20 | 130 | 4000 |
4890331 | Set – single with wedge shape | 35 | 145 | 4000 |
4890411 | Set – single with wedge clamp | 10 | 90 | 4000 |
4890421 | Set – single with wedge clamp | 20 | 130 | 4000 |
4890431 | Set – single with wedge clamp | 35 | 145 | 4000 |
4890312 | Set – single with wedge wedge | 10 | 90 | 4000 |
4890322 | Set – single with wedge wedge | 20 | 130 | 4000 |
4890332 | Set – single with wedge wedge | 35 | 145 | 4000 |
4890412 | Set – single with wedge clamp | 10 | 90 | 4000 |
4890422 | Set – single with wedge clamp | 20 | 130 | 4000 |
4890432 | Set – single with wedge clamp | 35 | 145 | 4000 |
POST SILICONE INSULATOR
Post silicone insulators are used for middle voltage non-insulated aerial networks from 10 kV to 35 kV. They are made according to IEC 61109 standards. They are standardly produced with steel bolts M24/140 mm, and at customers demand we can make them with steel bolts from M20 to M36, with different lengths from 40mm to 200mm. Corrosion protection is achieved with hot dip galvanization.
Code number | Type of Insulator | Rated network voltage kV | Rated working voltage kV | Creeping distance mm | Dry lighting impulse withstand voltage kV | Wet power-freg, with stand voltage kV | Breaking force kN | Weight kg/pcs |
4890610 | PSI 12-M24/140 | 10 | 12 | 365 | 125 | 50 | 15 | 2.50 |
4890620 | PSI 24-M24/140 | 20 | 24 | 539 | 165 | 75 | 15 | 2.70 |
4890630 | PSI 38-M24/140 | 30 | 38 | 684 | 182 | 94 | 12.5 | 2.95 |